SPC

SPC

digital measuring transducer

  • IEC 870-5-1-95 (FT3)
  • IEC 60870-5-101
  • MODBUS

SPC digital measuring transducers digitize AC current, voltage, power and frequency signals in three-phase, three-wire and four-wire electrical circuits. SPC units also convert measured quantities into ±5 mA DC signals and process binary signals from volt-free contacts.

Request a quote

SPC digital measuring transducers convert AC current, voltage, power and frequency measurements in three-phase, three-wire and four-wire circuits into digital data.

SPC units also convert measured quantities into ±5 mA DC signals and process binary signals from volt-free contacts.

Design

The transducers are housed in plug-in plastic enclosures. The cover is secured to the connector section with four screws and has two latches that lock the transducer into its mating connector. The input connector is similar to a conventional BI-6 test block. It shorts the current circuits when the transducer is withdrawn and permits current-injection testing and insulation testing of incoming cables. Guide ribs between connector contacts prevent short circuits if the transducer is accidentally tilted during insertion. The mating connector has M4 screw terminals for the input and output circuits.

Applications

automated monitoring and control systems, SCADA systems, and automated electricity metering and monitoring systems at power utilities and other industrial facilities.

SPC
SPC digital measuring transducer
By connection arrangement and nominal input ratings
Designation Nominal input ratings Connection diagram
Current, A Voltage, V
SPC-100/1-4 3 × 1 3 × 57.7 Four-wire
SPC-100/1-3 2 × 1 3 × 100 Three-wire
SPC-100/5-4 3 × 5 3 × 57.7 Four-wire
SPC-100/5-3 2 × 5 3 × 100 Three-wire
SPC-380/5-4 3 × 5 3 × 220 Four-wire
Additional options
SPC-x/x-x SPC-x/x-x-T2 SPC-x/x-x-T3
AC supply: 187–253 V + + +
Universal power supply 120–370 V DC or 90–264 V AC - + +
Current outputs ±5 mA (±20 or 4–20 mA on request) - - 3 units
Inputs for four volt-free contacts 4 4 4
Volt-free contact sensing voltage 30–48 V 30 V 30 V
Model designation:
        SPC-100/5-4-T3 | | | | |_____ additional options | | | |________ SPC measurement circuit connection | | | 3 — three-wire | | | 4 — four-wire | | |__________ rated input current | | 1 — 1 A | | 5 — 5 A | |_____________ rated line-to-line input voltage | 100 — 100 V (57.7 V phase-to-neutral for four-wire connection) | 380 — 380 V (220 V phase-to-neutral for four-wire connection) |_________________ device type
SPC
SPC version with front connections

SPC units support three communication protocols, IEC 870-5-1-95 (FT3), IEC 60870-5-101 and MODBUS.
The protocol is specified when ordering and configured in software.
Measurement update interval: no more than 400 ms.

When ordering transducers with current outputs, specify the measured quantity assigned to each output and its full-scale value corresponding to 5 mA. If current output settings were not specified when ordering, configure them with the service program before commissioning.

Transducer operating conditions
Parameter Value
Ambient air temperature, °C 0…+55
Relative humidity, % 30…80
Atmospheric pressure, kPa 84…106

Supply voltage

SPC-xxx/x-x transducers have a standard supply voltage range and can be powered from an AC supply.

Parameter Value
Supply frequency, Hz 45…55
AC supply voltage, V 187…253

SPC-xxx/x-xT2 and SPC-xxx/x-xT3 transducers accept a wider supply voltage range and can operate from AC or DC supplies.

Parameter Value
Supply frequency, Hz 45…440
AC supply voltage, V 90…264
DC supply voltage, V 120…370

Supply power consumption does not exceed 7 VA.

Measured parameters by SPC variant
Parameter 4-wire connection Three-wire connection
Phase-to-neutral voltage on each phase yes no
Phase current in phases A and C yes yes
Phase current in phase B yes no
Line-to-line voltages AB and BC yes yes
Line-to-line voltage A–C yes yes
Active power for each phase yes no
Total three-phase active power yes yes
Reactive power for each phase yes no
Total three-phase reactive power yes yes
Apparent power per phase yes no
Average line-to-line voltage yes yes
Average phase-to-neutral voltage yes no
Average three-phase current yes yes
Power frequency yes yes
Input current and voltage phasor angles yes yes

Voltage and current measurements are RMS values.

SPC units with four-wire connections calculate line-to-line voltages from phase-to-neutral voltages.

Measurement ranges and rated values by variant
Parameter SPC-100/5-X-XX SPC-100/1-X-XX SPC-380/5-X-XX SPC-380/1-X-XX
range nominal range nominal range nominal range nominal
Phase-to-neutral voltage, V 0-69,3 57,735 0-69,3 57,735 0-264 220 0-264 220
Phase current, A 0-6 5 0-1,2 1 0-6 5 0-1,2 1
Line-to-line voltages, V 0-120 100 0-120 100 0-456 380 0-456 380
Active power per phase, W 415,6 288,68 83,1 69,282 1584 1100 316,8 220
Total active power, W 1247 866,03 250 173,205 4752 3300 950,4 660
Phase reactive power, var 415,6 288,68 83,1 69,282 1584 1100 316,8 220
Total reactive power, var 1247 866,03 250 173,205 4752 3300 950,4 660
Power frequency, Hz 47,5-52,5 50 47,5-52,5 50 47,5-52,5 50 47,5-52,5 50
Specified metrological characteristics
Measured quantity Maximum permissible intrinsic error as a percentage of the reference value
Phase current, I ±0,3
Voltage, U ±0,3
Active power, P ±0,5
Reactive power, Q ±0,5
Frequency, F ±0,03
±5 mA DC outputs ±0,15

SPC-xxx/x-x, SPC-xxx/x-x-T2 and SPC-xxx/x-x-T3 units acquire, process and transmit binary status signals from volt-free contacts. SPC-xxx/x status input circuits have an isolated 30–60 V power supply; SPC-xxx/x-x-T2 and SPC-xxx/x-x-T3 units use 27–33 V. Closed-circuit current depends on circuit resistance and is typically 5–10 mA.

SPC-xxx/x-x-T3 units have isolated ±5 mA DC outputs that can represent any measured quantity. Factory current output settings are listed in the product data sheet.

SPC current and voltage measurement circuit burden at rated current and rated frequency does not exceed the following values.
  • 0.02 VA at Inom — 1 A
  • 0.5 VA at Inom = 5 A
Permissible measurement-circuit overloads
Parameter Exposure duration
Input voltage with a peak value of 500 V continuous
200 A pulse input current no more than 1 s
Parameter Value
RS-485 communication rate 1200, 9600, 19200 or 57600 baud
Built-in surge protection on RS-485 circuits 15 kV under IEC 61000-4-2
Analog measurement update interval 0.4 s
Binary status update interval 1 ms
Measurement timestamp accuracy up to 1 ms
Maximum time from request receipt to start of data output 2 ms
The following transducer parameters can be configured over RS-485:
  • RS-485 baud rate
  • voltage and current transformer ratios
  • current output settings

Weight 0.7 kg.

Transducer overall and mounting dimensions

Weight 7.6 kg.

Transducer module overall and mounting dimensions
SPC three-wire connection diagram, front view
SPC four-wire connection diagram, front view
Side connector wiring for SPC-XXX/X-X and SPC-XXX/X-X-T2
Side connector wiring for SPC-XXX/X-X-T3