AURA

AURA-08-K

Conventional Digital Fault Recorder (DFR)

The AURA-08 recorder has a modular design that allows individual modules, particularly input transducers, to be replaced quickly. Additional measurement channels can be fitted and configuration settings changed during service. The recorder measures and monitors electrical quantities under normal operating and fault conditions in power and industrial facilities. Where required, cabinets can be fitted with forced ventilation and automatic heating for installation in unheated rooms.

Request a quote

Design

The main unit has an aluminum-profile enclosure that provides electromagnetic shielding and the mechanical strength required for long-term industrial service.

  1. Modular design allows individual units, including input transducers, to be replaced quickly;
  2. The number of recorded parameters can be expanded by adding hardware during service;
  3. Configuration settings can be changed during service;
  4. Latched indication of recorder triggers;
  5. Latched indication of recorder faults;
  6. Relay contact output for trigger and fault indication;
  7. A test trigger can be used to check disturbance recording;
  8. Local and remote reset of trigger indications and fault alarms.

Configuration

The central unit model, input transducer configuration and number of binary input modules are selected from the measurement channel list prepared when ordering.

Upgrades

The recorder's channel count can be expanded in service by installing additional input transducers and binary input modules. If the central unit has insufficient analog inputs, additional analog signal concentrators can be installed, including in an additional cabinet. The software configuration is updated as required.

Equipment installation

Recorders are supplied:
  1. As individual modules for installation on existing panels
  2. As fully assembled panels with internal wiring completed
  3. In fully wired cabinets with front and rear access
  4. In cabinets with front access only, with equipment mounted on a swing frame.

Cabinets can be fitted with forced ventilation and automatic heating for installation in unheated rooms.

Applications

The AURA digital fault recorder measures and monitors electrical quantities under normal operating and fault conditions in power and industrial facilities.

The AURA-08-K recording unit is housed in an aluminum extrusion enclosure.

The central unit contains a processor board, a multichannel ADC, a binary signal switching module, a keypad and display module, and an alarm board.

Ethernet interfaces provide external communication. USB ports allow recorded disturbance files to be copied to a USB drive, and a COM port is available for connecting a precision time receiver.

The main unit has a fanless, dust-protected enclosure. It is powered by an external 24 V DC power supply accepting 120–370 V DC or 85–264 V AC. Two power supplies can be fitted on request for redundancy, including operation from two independent supplies.

The front panel of the main unit contains:
  • LED indicators and a character display;
  • buttons for viewing status, triggering a test recording and resetting alarms.
The rear panel of the main unit contains:
  • connectors for analog input transducer modules (up to 256 channels);
  • connectors for binary input units, supporting up to 512 channels;
  • the recorder power button;
  • a connector for the 24 V DC power supply;
  • terminal block for external alarm circuits;
  • Ethernet ports;
  • processor board connectors for external devices

Operating system — AURA Linux, listed in the Russian Software Register.

Input transducers

AURA transducers are housed in standardized plug-in plastic enclosures, with four channels per enclosure. The cover is secured to the connector section with four screws and has two latches that lock the transducer into its mating connector. The input connector is similar to a conventional BI-6 test block. It shorts the current circuits when a transducer is withdrawn and permits current-injection testing and insulation testing of the incoming cables. Guide ribs between the connector contacts prevent short circuits if the transducer is accidentally tilted during insertion. The mating connector has M4 screw terminals for the input and output circuits. Different transducer types use different enclosure colors, and their mating connectors are color-matched.

Voltage transducer

The transducers are grouped into modules with mounting provisions for a standard protection panel or cabinet. Where a large number of channels is required, the transducer modules can be installed in an additional cabinet alongside the main cabinet.

Input transducers assembled in a module

Each module accommodates up to eight input transducers in any order. The rear of the module carries a recorder connector and routing channels for input wiring harnesses. Modules have an LED indicator and a power switch.

Available transducer variants
Part number
Name Specifications
AC voltage transducer
TVGTs.01.2209-250VPN-250ranges: 250 V, 160 V, 120 V, 80 V
AC current transducer
TVGTs.01.2609-20APT-20ranges: 20 A, 10 A, 4 A, 2 A
TVGTs.01.2609-200APT-200 ranges 200 A, 100 A, 40 A, 20 A
DC and AC voltage transducer
TVGTs.01.2909-0.2VPPN-0.2ranges: ±0.2 V / ±5 V
TVGTs.01.2909-24VPPN-24ranges: 24 V DC / 20 V AC
TVGTs.01.2909-330VPPN-330ranges 330 V DC / 250 V AC
TVGTs.01.2909-600VPPN-600ranges: 600 V DC / 600 V AC
DC and AC current transducer
TVGTs.01.2709-20mAPPT-0.02ranges: ±20 mA / ±5 V
TVGTs.01.2709-200mAPPT-0.2 ranges: ±200 mA / ±5 V

BKD

The BKD-64 binary input module provides connections and galvanic isolation for 64 volt-free contact inputs. A terminal block connects the incoming cable, and a 15-pin output connector connects the module to the recorder's central unit. A green LED indicates that power is on. Input circuits are supplied by an internal isolated 24 V power supply. The BKD-64 itself receives power from the AURA-08 central unit through the connecting cable. BKD-64 modules are normally mounted on the terminal mounting sides of panels or cabinets with front and rear access, or on the rear wall of front-access cabinets. Channel common wires can be joined at the connection point or at intermediate panels and brought to the module on a single wire. Additional common terminals can be installed above the BKD if required. For a large number of channels, BKD-64 modules can be installed in an additional cabinet beside the main cabinet.

BKD
Variant 1
BKD
Version 2

BKA board types used in AURA-256, AURA-128 and AURA-64 recorders

Three types of analog multiplexer boards have been used in AURA-256, AURA-128 and AURA-64 recorders:

1. AOUT64

64-input switching module.
Manufactured through 2009.

AOUT64

Used in AURA recorder models with separate concentrators in steel enclosures, and in aluminum extrusion enclosures with Mini-ITX processor boards: EPIA ML5000, EPIA V5000, EPIA ME6000, EPIA LN10000 or NEX620.

2. BKA_2.1 (part number SVE.01.1107.250)

32-input multiplexer board.
Manufactured from November 11, 2009 to November 20, 2014.

The 64-input BKA_2.1 multiplexer assembly consists of two BKA_2.1 boards mounted on an aluminum rail.

BKA_2.1

To purchase a BKA_2.1 module, order two BKA_2.1 boards (part no. SVE.01.1107.250) and one mounting strip (part no. SVE.01.1107.000.01).

3. BKA_3.1 (part number SVE.01.1109.250)

32-input multiplexer board.
Manufactured since December 23, 2014.

The 64-input BKA_3.1 multiplexer assembly consists of two BKA_3.1 boards mounted on an aluminum panel.
Used in AURA-256 recorders with aluminum-profile enclosures and an MS-98D1 processor board, or in AURA-08-K1 recorders with an EPIC-BT07 processor board.

BKA_3.1
The panel is available in four versions that differ only in their labels.
  1. BKA panel marked “A1,A2” (part number SVE.01.1109.000.02)
  2. BKA panel labeled “A3,A4” (part no. SVE.01.1109.000.02-01)
  3. BKA panel marked “A5,A6” (part number SVE.01.1109.000.02-02)
  4. BKA panel labeled “A7,A8” (part no. SVE.01.1109.000.02-03)

To purchase a BKA_3.1 unit, order two BKA_3.1 boards and one panel.

Note

The manufacture dates of BKA boards may differ from those of the AURA recording units in which they are fitted. Recorders manufactured from 2016 onward use BKA_3.1 boards. For earlier recorders, compare the fitted boards with the photographs shown.
Recorder specifications
  • ADC resolution: 12 or 16 bits, depending on the main unit model
  • Triggers: any analog or binary channel, calculated channels, including U2(I2) and 3U0(3I0)
  • Cabinet supply 220/110 V DC, 220/127 V AC
  • Binary alarm output specifications:
    • Switching voltage up to 400 V
    • Switching current up to 50 mA
  • Storage: flash drive, 240 GB minimum.
  • Communication: 10/100/1000 Mbps Ethernet
  • Operating temperature range: +1 to +45 °C
  • Climatic category: UHL4 or O4 under the Russian classification

The recorder complies with GOST R 58601-2019.
AURA-08 recorders are listed in the Russian State Register of Measuring Instruments, registration no. 90938-23.

Accuracy class:
AC current and voltage: 0.5%
DC current and voltage — 0.5%
phase displacement: 1 degree
frequency — 0.05 Hz

  1. recording AC and DC voltage and current signals by capturing instantaneous values and digitizing them as a sequence of amplitude- and time-quantized samples at the configured sampling rate;
  2. calculating RMS values, mean values and symmetrical components of analog signals by digitally processing the recorded samples;
  3. determining the fundamental frequency of the recorded AC current and voltage signals;
  4. recording binary signal states;
  5. saving recorded values and their associated attributes, including timestamps, channel names, transformer ratios and sampling rate, in IEEE Std C37.111 COMTRADE 2013 format;
  6. providing secure remote access to recorder data;
  7. capturing network traffic while recording disturbance waveforms. Captured traffic is saved to a *.pcap file for viewing and analysis in suitable software such as Wireshark. A built-in traffic analyzer is available from AuraQt v1.2.0.0;

Data storage and transfer

Disturbance files remain in the recorder's nonvolatile memory until deleted.

Files can be deleted in the following ways.
  1. manually;
  2. automatically after a new recording, by deleting the oldest file when disk usage reaches 80%;
  3. On a large drive, the number of files can reach several thousand, making them harder to manage. The recorder allows a maximum file count to be set. When a new recording exceeds this limit, the oldest excess file is deleted automatically.
At the recorder installation site, data can be retrieved in the following ways.
  1. By connecting a laptop to the recorder’s Ethernet interface. A standard web browser, such as Google Chrome, provides access to the recorder over a secure connection using digital certificates. Access rights can be assigned according to the user permissions specified in the digital certificate.
  2. By copying files directly from the recorder to a USB flash drive. When a drive is inserted into the recorder’s USB port, recent disturbance files that have not yet been copied are copied automatically, together with a transfer report. Individual files can also be selected and copied using the main unit keypad.
The recorders support several ways of delivering disturbance data to remote clients:
  1. downloading files directly through the web interface using a standard browser such as Google Chrome. Connections are secured with digital certificates. Access permissions can be assigned according to the user privileges specified in the certificate;
  2. automatically sending data to specified servers over FTP(S), SFTP or IEC 61850-8-1 MMS.
Live measured values are available over the following protocols.
    IEC 60870-5-104 and IEC 61850-8-1 MMS.