PR-4N and PR-4T measuring transducers measure instantaneous and phasor values of AC voltage and current, monitor volt-free contact states, and transmit this information over Ethernet to higher-level measurement systems.
Request a quoteThese versatile measuring transducers use modern components to support automation systems on a common hardware platform from one manufacturer, including synchrophasor monitoring, SCADA, disturbance recording and fault location. IEC 61850 support and standard communication protocols allow integration into existing process control systems. PR-4N and PR-4T transducers measure instantaneous and phasor values of AC voltage and current, monitor volt-free contact states, and transmit the information over Ethernet to higher-level measurement systems.
The transducers are housed in plug-in plastic enclosures. The cover is secured to the connector section with four screws and has two latches that lock the transducer into its mating connector. The input connector is similar to a conventional BI-6 test block. It shorts the current circuits when the transducer is withdrawn and permits current-injection testing and insulation testing of incoming cables. Guide ribs between connector contacts prevent short circuits if the transducer is accidentally tilted during insertion. The mating connector has M4 screw terminals for the input and output circuits.
The transducers are used in digital fault recorders, synchrophasor measurement and monitoring systems, SCADA systems and other automated information and measurement systems at power utilities and industrial facilities.
Several versions are available with different input signal types and measurement ranges. Every version has four independent measurement channels and four binary inputs for volt-free contacts.
| Designation | Analog inputs | Binary inputs | |
|---|---|---|---|
| Current | Voltage | ||
| PR-4N350 | - | 4 (350 V AC) | 4 (24 V DC) |
| PR-4T20 | 4 (20 A AC) | - | 4 (24 V DC) |
| PR-4T200 | 4 (200 A AC) | - | 4 (24 V DC) |
For analog inputs, the value in parentheses is the measurement range in RMS AC current or voltage. For binary inputs, it is the nominal operating voltage.
| Functions | Communication protocols | Software | Note |
|---|---|---|---|
| Synchrophasor monitoring system | IEEE C37.118 (TCP, UDP) | AuraPDC | Connect to an accuracy class 0.5 current-transformer core. AURA-SMPR and AURA SCADA functions can operate simultaneously. |
| SCADA | IEC 60870-5-104 | AuraMaster | |
| Digital Fault Recorder (DFR) | COMTRADE, IEC 60870-5-104 | AuraServ, Aura2000, PostAWR, TeleAURA | Connected to a class 10P CT core. AURA recording, AURA-61850 and fault location functions are implemented in a single hardware and software system. |
| IEC 61850 (GOOSE, SV) | AuraRec | ||
| Fault location | FTP, SMB | Aura2000 |